Toshiba RAV-SM563UT-E Service Manual/Integration page 119

Air-conditioner split type
Hide thumbs Also See for RAV-SM563UT-E:
Table of Contents

Advertisement

n Confirmation of indoor unit No. position
1. To know the indoor unit addresses though position of the indoor unit body is recognized
• In case of individual operation (Wired remote controller : indoor unit = 1 : 1)
(Follow to the procedure during operation)
<Procedure>
1
ON / OFF
Push
button if the unit stops.
2
UNIT
Push
button.
1-1
Unit No.
is displayed on LCD.
(It disappears after several seconds.)
The displayed unit No. indicate line address and
indoor unit address.
(When other indoor units are connected to the
identical remote controller (Group control unit), other
unit numbers are also displayed every pushing
button.
2. To know the position of indoor unit body by address
• To confirm the unit No. in the group control
(Follow to the procedure during operation) (in this procedure, the indoor units in group control stop.)
<Procedure>
The indoor unit numbers in the group control are succes-
sively displayed, and fan, louver, and drain pump of the
corresponding indoor unit are turned on.
(Follow to the procedure during operation)
1
VENT
TEST
Push
and
buttons simultaneously for
4 seconds or more.
ALL
• Unit No.
is displayed.
• Fans and louvers of all the indoor units in the
group control operate.
2
UNIT
Every pushing
in the group control are successively dis-
played.
• The unit No. displayed at the first time indicates the
master unit address.
• Fan and louver of the selected indoor unit only
operate.
3
TEST
Push
button to finish the procedure.
All the indoor units in the group control stop.
Tel: 01823 665660
Heronhill - for all your Toshiba requirements
button, the unit numbers
– 119 –
www.heronhill.co.uk
TEMP.
FILTER
RESET TEST
UNIT
<Operation procedure>
1
2
END
SET
DATA
TEMP.
1
FILTER
RESET TEST
3
<Operation procedure>
1
2
3
UNIT No.
ON / OFF
Operation
TIMER SET
FAN
MODE
TIME
SWING/FIX
VENT
SET CL
UNIT
UNIT No.
R.C.
No.
ON / OFF
TIMER SET
FAN
MODE
TIME
SWING/FIX
VENT
SET CL
UNIT
END
Fax: 01823 665807
1
2
2

Hide quick links:

Advertisement

Table of Contents
loading