No.
Part name
ˆ
1. Detachment
Drain pump
assembly
1) Perform works of items 1 of
2) Picking the hose band, slide it from
3) Remove screw fixing the drain pump
3. Attachment
1) Fix the drain pump assembly as before.
NOTE :
The drain pump is fixed with a hook and 3
screws. In screwing, be sure that screws
do not to run on hooking claw at the main
body side.
2) Attach the drain hose and hose band as
NOTE :
Insert the drain hose up to the end of
pump connecting part, and bind the white
mark position of the hose with band.
Tel: 01823 665660
Heronhill - for all your Toshiba requirements
Procedure
ƒ
1 of
, 1 of
and 1 of
pump connecting part to remove the
drain hose.
assembly, slide hooking claws of the
drain pump assembly and the main
body (1 position), and then remove the
assembly. (Ø4 × 8, 3 pcs.)
before.
– 125 –
www.heronhill.co.uk

, 1 of
,
Slide to hose side.
Slide to hose side.
.
Hose band
Hose band
Hooking claw
Hooking claw
Hooking cla
Fixing screw
Fixing screw
Fixing scre
Remarks
Pump connecting part
Pump connecting part
Pump connecting par