Parameter
6.23.3
PID set point direct setting menu
The setting menu is used to input the PID set point (Pr. 133, Pr. 755) in simple steps under PID
control. Pressing the "FUNC" key while the FR-PU07-01 is in the monitor mode starts the direct
setting mode for the PID set point.
(Valid under PID control. If the "FUNC" key is pressed while the PID control is invalid, the func-
tion menu is displayed.)
P I D s e t
SET
FUNC:FUNC MENU
Direct setting mode 1 (Pr. 133)
SET
FUNC:FUNC MENU
Direct setting mode 2 (Pr. 755)
Fig. 6-228: Procedure for direct setting of PID set point
NOTE
In the direct setting mode, parameters can be always read or written regardless of the Pr. 77
and Pr. 160 settings.
FR-F700 EC
0. 0
P S I
- - - S T OP HAND
Monitor mode
P I D s e t p n t 1
80.0PSI
P I D s e t p n t 2
40.0PSI
1 M O N I T O R
2 P U O p e r
3 P r . L i s t
4 P r . C l e a r
Function menu
PI D s e t p n t 1
SET
80.0PSI
to
40.0PSI
S E T
0~ 5 0 0
Direct setting mode 1 (Pr. 133)
Change the value with the numeric
keypad.
Using
/
PI D s e t p n t 2
to
SET
40.0PSI
S E T
20.0PSI
0~ 5 0 0
Direct setting mode 2 (Pr. 755)
Change the value with the numeric keypad.
Using
/
Setting of FR-PU07-01
Writing of the set value
is completed.
The setting is applied to
the PID action.
change the value
Writing of the set value
is completed.
The setting is applied to
the PID action.
change the value