Frequency Setting; Direct Setting - Mitsubishi Electric FR-PU07 Instruction Manual

Parameter unit
Hide thumbs Also See for FR-PU07:
Table of Contents

Advertisement

FUNCTIONS
2.2

Frequency Setting

The frequency in PU operation mode and external/PU combined operation mode (Pr. 79 = "3") can be set.
REMARKS
When changing the operation mode from external operation mode to PU operation mode, operation mode can not be changed if the external starting
signal (STF or STR) is on.

2.2.1 Direct setting

Directly enter a frequency setting using the number keys.
Example: Operation procedure (Changing from 0 Hz setting to
50 Hz setting)
Description
Press the PU-key.
The frequency setting screen appears.
Enter 50 Hz using the number keys.
Press the WRITE-key.
The 50 Hz setting is complete.
If you entered an incorrect value, press the ESC-key to return to the
pre-entry state.
18
Display
Freq Set
SET
0.00Hz
0~400Hz
Freq Set
SET
0.00Hz
50.00Hz
0~400Hz
Freq Set
SET
50.00Hz
Completed