Setting Items And Set Data - Mitsubishi Electric 800 Series Instruction Manual

Rs-485 interface board, rs-485 communication terminals
Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

Caution
Always set the communication check time interval before starting operation to prevent hazardous conditions.
Data communication is not started automatically but is made only once when the computer provides a communication request.
If communication is disabled during operation due to signal cable breakage etc., the inverter cannot be stopped. When the
communication check time interval has elapsed, the inverter will trip (E.SER).
The inverter can be coasted to a stop by switching ON the RES signals or by switching the power OFF.
If communication is broken due to signal cable breakage, computer fault etc., the inverter does not detect such a fault. This
should be fully noted.
4.4.9

Setting items and set data

• After completion of parameter settings, set the instruction codes and data, then start communication from the computer to
allow various types of operation control and monitoring.
Read/
Instruction
Item
write
Read
H7B
Operation mode
Write
HFB
code
H0000: Network operation
H0001: External operation
H0002: PU operation, External/PU combined operation, PUJOG operation
H0000: Network operation
H0001: External operation
H0002: PU operation (RS-485 communication operation via PU connector)
Data description
Number of
data digits
(Format)

4 digits
(B.E/D)
4 digits
(A,C/D)
47