Output Current Detection Function (Y12, Y13, Pr. 150 To Pr. 153, Pr. 166, Pr. 167) - Mitsubishi Electric FR-F740 EC Instruction Manual

Fr-f700 series
Table of Contents

Advertisement

Function assignment of external terminals
6.9.7

Output current detection function (Y12, Y13, Pr. 150 to Pr. 153, Pr. 166, Pr. 167)

The output power during inverter running can be detected and output to the output terminal.
Pr.
Name
No.
Output current detection
150
level
Output current detection
151
signal delay time
Zero current detection
152
level
Zero current detection
153
time
Output current detection
166
signal retention time
Output current detection
167
operation selection
The above parameters can be set when Pr. 160 = 0.
When Pr. 570 "Multiple rating setting" = 1, performing parameter clear changes the initial
value and setting range. (Refer to section 6.2.5.)
6 - 130
Initial
Setting
Description
Value
Range
Set the output current detection level.
0–120%
110%
100% is the rated inverter current.
Set the output current detection period.
Set the time from when the output current
0s
0–10s
has risen above the setting until the output
current detection signal (Y12) is output.
Set the zero current detection level.
5%
0–150%
The rated inverter current is assumed to be
100%.
Set this parameter to define the period
from when the output current drops below
0.5s
0–10s
the Pr. 152 value until the zero current
detection signal (Y13) is output.
Set the retention time when the Y12 signal
0–10s
is on.
0.1s
The Y12 signal on status is retained. The
9999
signal is turned off at the next start.
Y12 Signal - ON
0
Operation continued Operation continued
0
1
Fault stop (E.CDO)
10
Operation continued Fault stop (E.CDO)
11
Fault stop (E.CDO)
Parameters referred to
190–196
Y13 Signal - ON
Operation continued
Fault stop (E.CDO)
Parameter
Refer to
Section
Output terminal
6.9.5
function selection

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-f746 ec

Table of Contents