Connection Of The Power Regeneration Common Converter Fr-Cv; (01160 Or Less) - Mitsubishi Electric FR-F740 EC Instruction Manual

Fr-f700 series
Table of Contents

Advertisement

Connection of stand-alone option units
3.7.4

Connection of the power regeneration common converter FR-CV

(01160 or less)

When connecting the power regeneration common converter (FR-CV), make connection so that
the inverter terminals (P/+, N/−) and the terminal symbols of the power regeneration common
converter (FR-CV) are the same.
After making sure that the wiring is correct, set "2" in Pr. 30 "Regenerative function selection".
(Refer to section 6.8.2).
Fig. 3-32: Connection of the power regeneration common converter FR-CV
Remove the jumpers across the inverter terminals R/L1-R1/L11, S/L2-S1/L21, and connect
the control circuit power supply to the R1/L11 and S1/L21 terminals. Always keep the power
input terminals R/L1, S/L2, T/L3 open. Incorrect connection will damage the inverter. (E.OPT
(option alarm) will occur. (Refer to page 7-16.)
Opposite polarity of terminals N/−, P/+ will damage the inverter.
Do not insert the MCCB between terminals P/+-N/− (P/L+-P/+, N/L−-N/−).
Assign the terminal for X10 signal using any of Pr. 178 to Pr. 189 "Input terminal function
selection". (Refer to section 6.9.1.)
Be sure to connect the power supply and terminals R/L11, S/L21, T/MC1. Operating the
inverter without connecting them will damage the power regeneration common converter.
Be sure to connect terminal RDYB of the FR-CV to the X10 signal or MRS signal assigned
terminal of the inverter, and connect terminal SE of the FR-CV to terminal SD of the inverter.
Without proper connecting, FR-CV will be damaged.
NOTES
The voltage phases of terminals R/L11, S/L21, T/MC1 and terminals R2/L1, S2/L2, T2/L3
must be matched.
Use sink logic when the FR-CV is connected. The FR-CV cannot be connected when source
logic (factory setting) is selected.
3 - 40
3-phase AC
power supply
Dedicated stand-alone
Power regeneration
reactor FR-CVL
common converter FR-CV
Wiring
Inverter
M
3~
I001039E

Hide quick links:

Advertisement

Table of Contents
loading