Analog Output - Mitsubishi Electric FR-F740 EC Instruction Manual

Fr-f700 series
Table of Contents

Advertisement

Communication operation and setting
Supported BACnet object
● Analog Input
Object
Identifier
0
1
2
Tab. 6-100: Object assignment for analog inputs
: Read only
● Analog Output
Object
Identifier
0
1
Tab. 6-101: Object assignment for analog outputs
/v: Read/Write (Commandable values supported)
Available regardless of the operation mode, operation command source and speed com-
mand source.
6 - 316
Present
Object Name
Value Access
Type
Terminal 1
Terminal 2
Terminal 4
Present
Object Name
Value Access
Type
Terminal CA
Terminal AM
Description
Represents actual input voltage of
terminal 1.
(The range varies depending on the Pr. 73
and Pr. 267 settings.
–10 to +10V (–100% to +100%),
–5 to +5V (–100% to +100%) )
Represents actual input voltage (or input
current) of terminal 2.
(The range varies depending on the Pr. 73
and Pr. 267 settings.
0 to 10V (0% to 100%), 0 to 5V (0% to
100%), 0 to 20 mA (0% to 100%) )
Represents actual input voltage (or input
current) of terminal 4.
(The range varies depending on the Pr. 73
and Pr. 267 settings.
2 to 10V (0% to 100%), 1 to 5V (0% to 10
0%), 4 to 20 mA (0% to 100%) )
Description
Controls actual output current level of ter-
minal CA.
/v
Control is available when Pr. 54 = "85"
(Setting range:
0.0% to 100.0% (0 to 20mA))
Controls actual output voltage level of
terminal AM.
/v
Control is available when Pr. 158 = "86"
(Setting range:
0.0% to 100.0% (0 to 10V))
Parameter
Unit
percent (98)
percent (98)
percent (98)
Unit
percent (98)
.
percent (98)
.