Installation
2.4

Enclosure design

When an inverter enclosure is to be designed and manufactured, heat generated by contained
equipment, etc., the environment of an operating place, and others must be fully considered to
determine the enclosure structure, size and equipment layout. The inverter unit uses many
semiconductor devices. To ensure higher reliability and long period of operation, operate the in-
verter in the ambient environment that completely satisfies the equipment specifications.
2.4.1

Inverter installation environment

As the inverter installation environment should satisfy the standard specifications indicated in
the following table, operation in any place that does not meet these conditions not only deteri-
orates the performance and life of the inverter, but also causes a failure. Refer to the following
points and take adequate measures.
Item
Ambient
temperature
Ambient humidity
Atmosphere
Maximum altitude
Vibration
Tab. 2-1: Environmental standard specifications of inverter
Temperature
The permissible ambient temperature of the inverter FR-F740 is between −10 and +50°C (when
LD is set) or −10 and +40°C (when SLD is set) and of the inverter FR-F746 is between −10 and
+40°C (when LD is set) or −10 and +30°C (when SLD is set). Always operate the inverter within
this temperature range. Operation outside this range will considerably shorten the service lives
of the semiconductors, parts, capacitors and others. Take the following measures so that the
ambient temperature of the inverter falls within the specified range.
● Measures against high temperature
– Use a forced ventilation system or similar cooling system. (Refer to page 2-10.)
– Install the enclosure in an air-conditioned electrical chamber.
– Block direct sunlight.
– Provide a shield or similar plate to avoid direct exposure to the radiated heat and wind
of a heat source.
– Ventilate the area around the enclosure well.
● Measures against low temperature
– Provide a space heater in the enclosure.
– Do not power off the inverter. (Keep the start signal of the inverter off.)
● Sudden temperature changes
– Select an installation place where temperature does not change suddenly.
– Avoid installing the inverter near the air outlet of an air conditioner.
– If temperature changes are caused by opening/closing of a door, install the inverter away
from the door.
FR-F700 EC
FR-F740
−10 °C to +50°C
150 % overload
capacity
(non-freezing)
−10 °C to +40°C
120 % overload
capacity (Initial setting)
(non-freezing)
90% RH or less (non-condensing)
Free from corrosive and explosive gases, dust and dirt
1000m or less
5.9m/s² or less (2.9m/s² or less for the 04320 or more)
at 10 to 55Hz (directions of X, Y, Z axes)
Enclosure design
FR-F746
−10°C to +40°C
(non-freezing)
−10°C to +30°C
(non-freezing)
2 - 7