Pid Set Point (Network Input Snvt_Lev_Percent Nviinvpidtarget) - Mitsubishi Electric FR-A7NL Instruction Manual

Inverter plug-in option
Hide thumbs Also See for FR-A7NL:
Table of Contents

Advertisement

6.6.1

PID set point (network input SNVT_lev_percent nviInvPIDTarget)

Enter the target value of air volume, temperature or the like in 0.005% increments.
Data Name
nviInvPIDTarget
⋅ Data acceptance timing ........... At network variable receive (nv_update_occurs event)
Example:
When setting 30°C as the set point using a 10°C/0% and 50°C/100% detector,
(30 - 10)
× 100 = 50%
(50 - 10)
REMARKS
⋅ Control can not be exercised at less than the minimum resolution (0.01%) of the inverter.
⋅ When the value outside of the range is input, the input value is made invalid and the inverter operates with the value
set last time.
Initial Value
0.000%
. As the PID set point, input 50.00%.
NETWORK VARIABLES
Range
0.00% to 100.00%
Increments
0.005%/bit
57
6