AC Power and Backup Battery

The LYNX is powered by a 9VAC, 15VA Plug-in Transformer, ADEMCO 1332.
Refer to the wiring table below for wire gauge and length.
Distance of Transformer from the Control
Backup battery is required. In the event of an AC power loss, the Control is supported by the backup battery.
The battery is supervised for connection and for low voltage conditions. If the battery is missing, or a low battery
condition is detected, a "low battery" message is displayed and a report is sent to the central station. In addition, the
system will beep once every 3 minutes to audibly indicate a low battery condition (press any key to stop the
beeping).
The system uses either a single 9-volt alkaline battery (e.g., Duracell PC1604 Procell) or six 1.5V "AA" alkaline
batteries (e.g., Duracell MN1500). Select the appropriate battery(ies) based on the installation's UL requirement.
Install the batteries in the battery drawer as shown below.
8 /
1. Connect wires from the 1332 AC
Transformer to terminals 15 and 16
as shown in the wiring diagram.
After all wiring connections have
been made, plug the transformer
into a 24 hour 110VAC unswitched
outlet.
2. Slide out the battery drawer.
Install either a single 9V alkaline
battery or six 1.5V "AA" alkaline
batteries.
After installing the battery(ies), slide
the battery drawer into the back
plate only after AC power has been
applied.
Up to 75 feet
75 to 150 feet
150 to 300 feet
Wiring to the AC Transformer must not exceed 300 feet using 16 gauge wire. The
voltage reading between terminals 15 and 16 of the control must not fall below
9.00VAC (AC indicator turns off).
Do not plug the transformer into the AC outlet until after all wiring connections
have been made.
For UL985, you must use six 1.5V "AA" alkaline batteries (Duracell MN1500 only).
DO NOT slide the battery drawer with batteries installed back into the unit until
after AC power has been applied.
Wire Gauge to Use
#20
#18
#16
RJ11
HANDSET
INCOMING
PHONE
PHONE
LINE
–8–
BATTERY DRAWER
TYPICAL
9-VOLT
ALKALINE
BATTERY
(1)
BATTERIES ONLY
16
1
RJ31
LOCAL
RIBBON CABLE TO
SOUNDER
FRONT PCB ASSEMBLY
JUMPER
LINE
CUT = DISABLE
TYPICAL 1.5V
ALKALINE "AA"
BATTERY (6)
USE ALKALINE
ONE 9-VOLT
OR
SIX 1.5V "AA"
WIRING
TERMINALS