Mitsubishi Electric F700 Instruction Manual page 98

Hide thumbs Also See for F700:
Table of Contents

Advertisement

Parameter
Name
Electronic bypass
135
sequence selection
MC switchover
136
interlock time
137
Start waiting time
Bypass selection at
138
a fault
Automatic
switchover
139
frequency from
inverter to bypass
operation
Automatic
switchover
frequency range
159
from bypass to
inverter operation
140
143
Refer to Pr.29.
to
144
Refer to Pr.37.
PU display
145
language selection
148,149
Refer to Pr.22 and Pr.23.
Incre
Initial
Range
ments
Value
0
Without electronic bypass sequence
1
0
1
With electronic bypass sequence
Set the operation interlock time of MC2 and
0.1s
1s
0 to 100s
MC3.
Set the time slightly longer (0.3 to 0.5s or
0.1s
0.5s
0 to 100s
so) than the time from when the ON signal
enters MC3 until it actually turns on.
Inverter output is stopped (motor coast) at
0
inverter fault.
Operation is automatically switched to
1
0
bypass operation at inverter fault (Not
1
switched when an external thermal relay
operation (E.OHT) or CPU fault (E.CPU)
occurs)
Set the frequency to switch inverter
0 to 60Hz
operation to bypass operation.
0.01Hz
9999
9999
Without automatic switchover
Valid during automatic switchover operation
(Pr.139 ≠ 9999)
When the frequency command decreases
below (Pr.139 - Pr.159) after operation is
switched from inverter operation to bypass
operation, the inverter automatically
0 to 10Hz
switches operation to inverter operation
and operates at the frequency of frequency
command.
When the inverter start command (STF/
0.01Hz
9999
STR) is turned off, operation is switched to
inverter operation also.
Valid during automatic switchover operation
(Pr.139 ≠ 9999)
When the inverter start command (STF/
STR) is turned off after operation is
9999
switched from inverter operation to bypass
operation, operation is switched to inverter
operation and the motor decelerates to
stop.
0
Japanese
1
English
2
Germany
3
French
1
0
4
Spanish
5
Italian
6
Swedish
7
Finnish
Parameter list
Para
meter
copy
Description
All
Para
para
meter
meter
clear
clear
: enabled
× : disabled
4
×
×
91