Connection Of The Power Regeneration Converter (Mt-Rc) (75K Or More); Connection Of The Power Factor Improving Dc Reactor (Fr-Hel) - Mitsubishi Electric F700 Instruction Manual

Hide thumbs Also See for F700:
Table of Contents

Advertisement

2.5.6

Connection of the power regeneration converter (MT-RC) (75K or more)

When connecting a power regeneration converter (MT-RC), perform wiring securely as shown below. Incorrect
connection will damage the regeneration converter and inverter. After connecting securely, set "1" in
Pr. 30 Regenerative function selection and "0" in Pr. 70 Special regenerative brake duty.
MCCB
Three-phase
AC power
supply
CAUTION
⋅ When using the FR-F700 series together with the MT-
RC, install a magnetic contactor (MC) at the input side of
the inverter so that power is supplied to the inverter after
1s or more has elapsed after powering on the MT-RC.
When power is supplied to the inverter prior to the MT-
RC, the inverter and the MT-RC may be damaged or the
MCCB may trip or be damaged.
⋅ Refer to the MT-RC manual for precautions for
connecting the power coordination reactor and others.
2.5.7

Connection of the power factor improving DC reactor (FR-HEL)

When using the DC reactor (FR-HEL), connect it between terminals P1-P/+.
For the 55K or less, the jumper connected across terminals P1-P/+ must be removed. Otherwise, the reactor will not
exhibit its performance.
For the 75K or more, a DC reactor is supplied. Always install the reactor.
CAUTION
⋅ The wiring distance should be within 5m.
⋅ The size of the cables used should be equal to or larger than that of the power supply cables (R/L1, S/L2, T/L3).(Refer to page 14)
MC1
MT-RCL
R
S
T
Inverter input power supply (MC2)
MT-RC power supply (MC1)
P1
P/+
Remove
the jumper.
Connection of stand-alone option units
Inverter
MC2
U
R/L1
V
S/L2
W
T/L3
R1/L11
S1/L21
DCL
P1
P1
P/+ N/
P
P
N
R2
R2
RES
STF
S2
S2
SD
T2
C
T2
B
A
R
S
RDY
T
R1
SE
S1
MT-RC
FR-HEL
I M
Reset signal
Alarm signal
Ready signal
ON
ON
1s or more
35
2

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-f720Fr-f740

Table of Contents