Causes and corrective actions
Operation Panel
Indication
Name
Description
Check point
Corrective action
Operation Panel
Indication
Name
Description
Check point
Operation Panel
Indication
Name
Description
Check point
Corrective action
Operation Panel
Indication
Name
Description
Check point
Corrective action
Operation Panel
Indication
Name
Description
Check point
Corrective action
Operation Panel
Indication
Name
Description
Check Point
Corrective Action
114
E.P24
24VDC power output short circuit
When the 24VDC power output from the PC terminal is shorted, this function shuts off the power output.
At this time, all external contact inputs switch off. The inverter cannot be reset by entering the RES
signal. To reset it, use the operation panel or switch power off, then on again.
· Check for a short circuit in the PC terminal output.
· Remedy the earth (ground) fault portion.
E.CDO
Output current detection value exceeded
This functions stops the inverter output when the output current exceeds the setting of Pr.150 Output
current detection level, or the output current falls below the setting of Pr.152 Zero current detection level.
This function is active when Pr. 167 Output current detection operation selection is set to "1, 10, 11".
When the initial value (Pr. 167 = "0") is set, this fault does not occur.
Check the settings of Pr. 150 Output current detection level, Pr. 151 Output current detection signal delay time,
Pr. 152 Zero current detection level, Pr. 153 Zero current detection time, Pr. 166 Output current detection signal
retention time, Pr. 167 Output current detection operation selection. (Refer to the chapter 4 of
Instruction Manual (applied).)
E.IOH
Inrush current limit circuit fault
Trips when the resistor of the inrush current limit circuit overheats. The inrush current limit circuit fault
· Check that frequent power ON/OFF is not repeated.
· Check that no meltdown is found in the primary side fuse (5A) in the power supply circuit of the
inrush current suppression circuit contactor (FR-F740-132K or more) or no fault is found in the power
supply circuit of the contactor.
· Check that the power supply circuit of inrush current limit circuit contactor is not damaged.
Configure a circuit where frequent power ON/OFF is not repeated.
If the problem still persists after taking the above measure, please contact your sales representative.
E.SER
Communication fault (inverter)
This function stops the inverter output when communication error occurs consecutively for more than
permissible retry count when a value other than "9999" is set in Pr. 335 RS-485 communication retry count
during RS-485 communication from the RS-485 terminals. This function also stops the inverter output if
communication is broken for the period of time set in Pr. 336 RS-485 communication check time interval.
Check the RS-485 terminal wiring.
Perform wiring of the RS-485 terminals properly.
E.AIE
Analog input fault
Trips when 30mA or more is input or a voltage (7.5V or more) is input with the terminal 2/4 set to
current input.
Check the setting of Pr. 73 Analog input selection and Pr. 267 Terminal 4 input selection. (Refer to the chapter
4 of
the Instruction Manual (applied).)
Either give a frequency command by current input or set Pr. 73 Analog input selection or Pr. 267 Terminal
4 input selection to voltage input.
E.PID
PID signal fault
If any of PID upper limit (FUP), PID lower limit (FDN), and PID deviation limit (Y48) turns ON during PID
control, inverter shuts off the output. This function is active under the following parameter settings: Pr.554 PID
signal operation selection ≠ "0,10", Pr.131 PID upper limit ≠ "9999", Pr.132 PID lower limit ≠ "9999", and Pr.553 PID
deviation limit ≠ "9999". This protective function is not active in the initial setting (Pr.554 = "0", Pr.131 = "9999",
Pr.132 = "9999", Pr.553 = "9999").
Check if the measured PID value is greater than the upper limit (Pr.131) or smaller than the lower limit (Pr.132).
Check if the absolute PID deviation value is greater than the limit value (Pr.553).
Make correct settings for Pr.131 PID upper limit, Pr.132 PID lower limit, Pr.553 PID deviation limit.
chapter 4 of
the Instruction Manual (applied))
FR-PU04
E.P24
FR-PU07
FR-PU04
Fault 14
FR-PU07
OC detect level
FR-PU04
Fault 14
FR-PU07
Inrush overheat
FR-PU04
Fault 14
FR-PU07
VFD Comm error
FR-PU04
Fault 14
FR-PU07
Analog in error
FR-PU04
Fault 14
FR-PU07
Fault