Overheat Protection Of The Motor By The Inverter (Pr. 9) - Mitsubishi Electric F700 Instruction Manual

Hide thumbs Also See for F700:
Table of Contents

Advertisement

Overheat protection of the motor by the inverter (Pr. 9)

3.3 Overheat protection of the motor by the inverter (Pr. 9)
Set the rated motor current in Pr. 9 Electronic thermal O/L relay to protect the motor from overheat.
Parameter
Number
9
Electronic thermal O/L relay
*1
Refer to page 134 for the rated inverter current value.
*2
The minimum setting increments are 0.01A for the 55K or less and 0.1A for the 75K or more.
Changing example
Change the Pr. 9 Electronic thermal O/L relay setting to 2.0A according to the motor rated current.
(FR-F740-0.75K)
1.
Screen at powering on
The monitor display appears.
2.
Press
operation mode.
3.
Press
setting mode.
4.
Turn
Electronic thermal O/L relay) appears.
5.
Press
set value.
6.
Turn
the set value to
7.
Press
CAUTION
· Protective function by electronic thermal relay function is reset by inverter power reset and reset signal input. Avoid
unnecessary reset and power-off.
· When two or more motors are connected to the inverter, they cannot be protected by the electronic thermal relay function.
Install an external thermal relay to each motor.
· When the difference between the inverter and motor capacities is large and the setting is small, the protective characteristics of
the electronic thermal relay function will be deteriorated. In this case, use an external thermal relay.
· A special motor cannot be protected by the electronic thermal relay function. Use an external thermal relay.
· PTC thermistor output built-in the motor can be input to the PTC signal (AU terminal). For details, refer to the chapter 4 of
the Instruction Manual (applied).
· Electronic thermal relay may not function when 5% or less of inverter rated current is set to electronic thermal relay setting.
46
Name
Initial Value
Rated inverter
current
Operation
to choose the PU
to choose the parameter
until "
"(Pr. 9
to show the present
(2.1A for 0.75K)
to change
"
". (2.0A)
to set.
By turning
, you can read another parameter.
·
Press
to show the setting again.
·
Press
twice to show the next parameter.
·
Setting Range
0 to 500A
55K or less
75K or more
0 to 3600A
*1
Display
PU indication is lit.
Flicker
Parameter setting complete!!
···
Description
*2
Set the rated motor current.
The parameter number
read previously appears.
Refer to page
134 for initial
value of the
inverter rated
current.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-f720Fr-f740

Table of Contents