Limiting The Maximum And Minimum Output Frequency (Pr. 1, Pr. 2) - Mitsubishi Electric F700 Instruction Manual

Hide thumbs Also See for F700:
Table of Contents

Advertisement

4.3

Limiting the maximum and minimum output frequency (Pr. 1, Pr. 2)

Parameter
Name
Number
1
Maximum frequency
2
Minimum frequency
Changing example
Limit the frequency set by the potentiometer,
etc. to 60Hz maximum.
(Set "60"Hz in Pr. 1 Maximum frequency.)
1.
Screen at powering on
The monitor display appears.
2.
Press
to choose the PU operation
mode.
3.
Press
to choose the parameter
setting mode.
4.
5.
Press
to read the present set value.
"
"(initial value) appears.
6.
Turn
to change it to the set
value "
7.
Press
to set.
REMARKS
· The output frequency is clamped by the Pr. 2 setting even if the set frequency is lower than the Pr. 2 setting (The frequency will
not decrease to the Pr. 2 setting.)
Note that Pr. 15 Jog frequency has higher priority than the minimum frequency.
· When the Pr. 1 setting is changed, frequency higher than the Pr. 1 setting can not be set by
· When performing a high speed operation at 120Hz or more, setting of Pr. 18 High speed maximum frequency is necessary.
(Refer to the chapter 4 of
If the Pr. 2 setting is higher than the Pr. 13 Starting frequency value, note that the motor will run at the set
frequency according to the acceleration time setting by merely switching the start signal on, without entry of
the command frequency.
Initial Value
55K or less
75K or more
0Hz
Operation
Pr. 1) appears.
".
· By turning
, you can read another parameter.
· Press
to show the setting again.
· Press
twice to show the next parameter.
the Instruction Manual (applied).)
CAUTION
Limiting the maximum and minimum
output frequency (Pr. 1, Pr. 2)
Setting
Range
120Hz
Set the upper limit of the output
0 to 120Hz
frequency.
60Hz
0 to 120Hz Set the lower limit of the output frequency.
Output frequency
(Hz)
Pr.1
Pr.18
Pr.2
0
(4mA)
Clamped at the
minimum frequency
Display
PU indication is lit.
The parameter
number read
previously appears.
Flicker ··· Parameter setting complete!!
Description
Clamped at the
maximum frequency
Frequency setting
5, 10V
(20mA)
.
67
4