Parameter list
Parameter
891
Refer to Pr.52.
892
Load factor
Energy saving
893
monitor reference
(motor capacity)
Control selection
during commercial
894
power-supply
operation
Power saving rate
895
reference value
896
Power unit cost
Power saving
897
monitor average
time
Power saving
898
cumulative monitor
clear
Operation time rate
899
(estimated value)
C0
FM terminal
(900)
calibration
C1
AM terminal
(901)
calibration
C2 (902)
to
Refer to Pr.125 and Pr.126.
———
C7 (905)
C42 (934)
to
Refer to Pr.127 to Pr.134.
———
C45 (935)
Parameter copy
989
alarm release
990
PU buzzer control
The parameter number in parentheses is the one for use with the parameter unit (FR-PU04/FR-PU07).
100
Incre
Initial
Name
ments
Value
0.1%
100%
Inverter
0.01/
rated
0.1kW
capacity
*16
1
0
1
9999
0.01
9999
1h
9999
1
9999
0.1%
9999
---
---
---
---
10/100
1
*17
1
1
Range
Description
Set the load factor for commercial power-
supply operation.
30 to 150%
This value is used to calculate the power
consumption estimated value during
commercial power supply operation.
Set the motor capacity (pump capacity).
0.1 to 55/
Set when calculating power saving rate and
average power saving rate value.
0 to 3600kW
*16 The setting depends on the inverter
*16
capacity (55K or less/75k or more)
0
Discharge damper control (fan)
1
Inlet damper control (fan)
2
Valve control (pump)
3
Commercial power-supply drive (fixed value)
Consider the value during commercial
0
power-supply operation as 100%
1
Consider the Pr.893 setting as 100%.
9999
No function
Set the power unit cost. Displays the power
0 to 500
saving rate on the energy saving monitor
9999
No function
0
Average for 30 minutes
1 to 1000h Average for the set time
9999
No function
0
Cumulative monitor value clear
1
Cumulative monitor value hold
Cumulative monitor continue
10
(communication data upper limit 9999)
Cumulative monitor continue
9999
(communication data upper limit 65535)
Use for calculation of annual power saving
amount. Set the annual operation ratio
0 to 100%
(consider 365 days
9999
No function
Calibrate the scale of the meter connected
---
to terminal FM.
Calibrate the scale of the analog meter
---
connected to terminal AM.
Parameters for alarm release at parameter
copy
10/100
*17 The setting depends on the inverter
*17
capacity (55K or less/75k or more)
0
Without buzzer
1
With buzzer
Para
meter
copy
: enabled
× : disabled
×
24h as 100%).
All
Para
para
meter
meter
clear
clear
×
×
×