Operation Panel
rE1
Indication
Name
Parameter read error
Description
An error occurred in the EEPROM on the operation panel side during parameter copy reading.
Check point
· Make parameter copy again. (Refer to page 73.)
Corrective action
· Check for an operation panel (FR-DU07) failure. Please contact your sales representative.
Operation Panel
Indication
Name
Parameter write error
1. You attempted to perform parameter copy write during operation.
Description
2. An error occurred in the EEPROM on the operation panel side during parameter copy writing.
Check point
Is the FWD or REV LED of the operation panel (FR-DU07) lit or flickering?
1. After stopping operation, make parameter copy again. (Refer to page 73.)
Corrective action
2. Check for an operation panel (FR-DU07) failure. Please contact your sales representative.
Operation Panel
Indication
Name
Parameter verification error
1. Data on the operation panel side and inverter side are different.
Description
2. An error occurred in the EEPROM on the operation panel side during parameter verification.
Check point
Check for the parameter setting of the source inverter and inverter to be verified.
1. Press
Corrective action
Make parameter verification again. (Refer to page 74.)
2. Check for an operation panel (FR-DU07) failure. Please contact your sales representative.
Operation Panel
Indication
Name
Model error
1. A different model was used for parameter write and verification during parameter copy.
Description
2. When parameter copy write is stopped after parameter copy read is stopped
1. Check that the verified inverter is the same model.
Check point
2. Check that the power is not turned off or an operation panel is not disconnected, etc. during
parameter copy read.
1. Use the same model (FR-F700 series) for parameter copy and verification.
Corrective action
2. Perform parameter copy read again.
Operation Panel
Indication
1. The RES signal is on
2. The PU and inverter cannot make normal communication (contact fault of the connector)
Description
3. When the voltage drops in the inverter's input side.
4. When the control circuit power (R1/L11, S1/L21) and the main circuit power(R/L1, S/L2, T/L3) are
connected to a separate power, it may appear at turning on of the main circuit. It is not a fault.
1. Turn off the RES signal.
Corrective action
2. Check the connection of the PU and inverter.
3. Check the voltage on the inverter's input side.
rE2
rE3
to continue verification.
rE4
Err.
Causes and corrective actions
-- -- -- - -- -- - --
5
105