Alarm 2 Type - Omron E5CN User Manual

Hide thumbs Also See for E5CN:
Table of Contents

Advertisement

Initial Setting Level

Alarm 2 type

Function
Setting
86
• Select one of the following alarm 2 types:
Deviation/Deviation range/Absolute value
Alarm Type
Set
Value
0
Alarm function OFF
*1 1
Upper- and lower-limit (deviation)
2
Upper-limit (deviation)
3
Lower-limit (deviation)
*1 4
Upper- and lower-limit range
(deviation)
*1 5
Upper- and lower-limit with
standby sequence (deviation)
6
Upper-limit with standby
sequence (deviation)
7
Lower-limit with standby
sequence (deviation)
8
Absolute-value upper-limit
9
Absolute-value lower-limit
10
Absolute-value upper-limit with
standby sequence
11
Absolute-value lower-limit with
standby sequence
Note
(1) With set values 1, 4 and 5, the upper and lower limit values can be set
independently for each alarm type, and are expressed as "L" and "H". De-
fault is set value "2".
The alarm 2 type must be supported.
The control must be set to standard
control.
Alarm Output Operation
When X is positive
When X is negative
Output OFF
*2
L H
ON
OFF
SP
X
ON
ON
OFF
OFF
SP
X
ON
ON
OFF
OFF
SP
*2
L H
ON
OFF
SP
*2
L H
ON
OFF
SP
X
ON
ON
OFF
OFF
SP
X
ON
ON
OFF
OFF
SP
X
ON
ON
OFF
OFF
0
X
ON
ON
OFF
OFF
0
X
ON
ON
OFF
OFF
0
X
ON
ON
OFF
OFF
0
Section 5-5
X
SP
X
SP
X
SP
X
SP
X
0
X
0
X
0
X
0