Alarm Type; Description Of Function - Omron E5 C Series Manual

Digital temperature controller
Hide thumbs Also See for E5 C Series:
Table of Contents

Advertisement

Alarm Types
Each alarm can be independently set to one of the following 17 alarm types. The default is 2: Upper limit. (See note.)
Auxiliary outputs are allocated to alarms. ON delays and OFF delays (0 to 999 s) can also be specified.
Note: In the default settings for models with HB or HS alarms, alarm 1 is set to a heater alarm (HA) and the Alarm Type 1 parameter is not displayed.
To use alarm 1, set the output assignment to alarm 1.
Set

Alarm type

value
0
Alarm function OFF
Upper- and lower-limit *1
1
2
Upper-limit
(default)
3
Lower-limit
Upper- and lower-limit
4
range *1
Upper- and lower-limit with
5
standby sequence *1
Upper-limit with standby
6
sequence
Lower-limit with standby
7
sequence
Absolute-value upper-
8
limit
9
Absolute-value lower-limit
Absolute-value upper-
10
limit with standby
sequence
Absolute-value lower-limit
11
with standby sequence
12
LBA (alarm 1 type only)
13
PV change rate alarm
SP absolute-value
14
upper-limit alarm
SP absolute-value
15
lower-limit alarm
MV absolute-value
16
upper-limit alarm *9
MV absolute-value
17
lower-limit alarm *9
Alarm output operation
When alarm value X
When alarm value X
is positive
is negative
Output OFF
L
H
*
ON
2
OFF
PV
SP
X
ON
ON
OFF
OFF
PV
SP
X
ON
ON
OFF
PV
OFF
SP
L
H
*
ON
3
OFF
PV
SP
L
H
*
ON
4
OFF
PV
*5
SP
X
ON
ON
OFF
PV
OFF
SP
X
ON
ON
OFF
OFF
PV
SP
X
ON
ON
OFF
PV
OFF
0
X
ON
ON
OFF
PV
OFF
0
X
ON
ON
OFF
OFF
PV
0
X
ON
ON
OFF
PV
OFF
0
-
-
X
ON
ON
OFF
SP
OFF
0
X
ON
ON
OFF
SP
OFF
0
Standard Control
Standard Control
X
ON
ON
OFF
MV
OFF
0
Heating/Cooling
Heating/Cooling
Control (Heating MV)
Control (Heating MV)
X
ON
Always ON
OFF
MV
0
Standard Control
Standard Control
X
ON
ON
OFF
MV
OFF
0
Heating/Cooling
Heating/Cooling
Control (Cooling MV)
Control (Cooling MV)
X
ON
Always ON
OFF
MV
0

Description of function

No alarm
Set the upward deviation in the set point for the alarm upper
limit (H) and the lower deviation in the set point for the alarm
lower limit (L). The alarm is ON when the PV is outside this
deviation range.
Set the upward deviation in the set point by setting the alarm
X
value (X). The alarm is ON when the PV is higher than the
PV
SP by the deviation or more.
SP
Set the downward deviation in the set point by setting the
X
alarm value (X). The alarm is ON when the PV is lower than
PV
the SP by the deviation or more.
SP
Set the upward deviation in the set point for the alarm upper
limit (H) and the lower deviation in the set point for the alarm
lower limit (L). The alarm is ON when the PV is inside this
deviation range.
A standby sequence is added to the upper- and lower-limit
alarm (1). *6
X
A standby sequence is added to the upper-limit alarm (2). *6
PV
SP
X
A standby sequence is added to the lower-limit alarm (3). *6
PV
SP
The alarm will turn ON if the process value is larger than the
X
alarm value (X) regardless of the set point.
PV
0
The alarm will turn ON if the process value is smaller than the
X
alarm value (X) regardless of the set point.
PV
0
A standby sequence is added to the absolute-value upper-
X
limit alarm (8). *6
PV
0
A standby sequence is added to the absolute-value lower-
X
limit alarm (9). *6
PV
0
*7
*8
This alarm type turns ON the alarm when the set point (SP)
X
is higher than the alarm value (X).
SP
0
This alarm type turns ON the alarm when the set point (SP)
X
is lower than the alarm value (X).
SP
0
X
MV
0
This alarm type turns ON the alarm when the manipulated
variable (MV) is higher than the alarm value (X).
X
MV
0
This alarm type turns ON the alarm when the manipulated
variable (MV) is lower than the alarm value (X).