Advanced Function Setting Level
pV-b
PV stable band
Function
Setting
See
104
This parameter sets the PV stable band width when the PV display color is
changed according to the PV stable band.
• When the mode linking to the PV stable band is selected, the PV display
color will change according to whether the present value (PV) is lower/
within/higher than the PV stable band shown in the following figure.
• The hysteresis width is fixed at 0.2 (EU).
Low
0.2 (EU)
Setting Range
0.1 to 999.9
Related parameters
"PV color change" (advanced function setting level) (page 103)
PV stable
PV stable
band
band
Within range
High
0.2 (EU)
SP
Unit
Default
EU