Advanced Function Setting Level
mspu
Multi-SP uses
Function
Setting
See
SP ramp set value
Function
Setting
See
When the "multi-SP uses" parameter is set to "ON", you can select set points
0 to 3 by operating the keys on the front panel of the controller.
When the option event input unit E53-CNHB is mounted on the E5GN, this
parameter can be used when the "number of multi-SP uses" parameter is set
to "0" and "multi-SP uses" is set to ON.
;::
You can select set points 0 to 3.
;22: You cannot select set points 0 to 3.
Related parameters
"Multi-SP" (operation level)
"Number of Multi-SP uses" (advanced function setting level)
• This parameter specifies the change rate during SP ramp operation. Set
the maximum permissible change width per unit of time (minute) as the
"SP ramp set value". However, note, that when the "SP ramp set value" is
set to "OFF", the SP ramp function is disabled.
• When setting "30 per minute" as the "SP ramp set value," set the "SP
ramp set value" parameter to "30".
• During temperature input, the decimal point position of the SP ramp set
value is dependent on the currently selected sensor, and during analog
input it is dependent on scaling.
Parameter
SP ramp set value
Related parameters
"Input type" "Scaling upper limit" "Scaling lower limit" "Decimal point" "ST" (ini-
tial setting level)
The "number of multi-SP uses"
parameter must be set to "0" on mod-
els on which the option event input
unit E53-CNHB is not mounted.
ST (self-tuning) must be set to
"OFF".
Setting Range
Unit
OFF, 1 to 9999
EU
Section 5-6
Default
OFF
91