Wiring Terminals; Mounting; Terminal Arrangement - Omron E5CN User Manual

Hide thumbs Also See for E5CN:
Table of Contents

Advertisement

Wiring Terminals

2-1-4

Mounting

How to attach the E5CN
on the panel
1,2,3...
How to attach the terminal
cover
2-2

Wiring Terminals

2-2-1

Terminal arrangement

Voltage output/relay
output/Current output
12
Terminal cover
1. Insert the E5CN into the mounting hole in the panel.
2. Push the adapter along the E5CN body from the terminals up to the panel,
and fasten temporarily.
3. Tighten the two fixing screws on the adapter. When tightening screws,
tighten the two screws alternately keeping the torque to approximately
0.29 to 0.39 N ⋅ m.
Make sure that the "UP" mark is facing up, and then fit the terminal cover
(E53-COV10) into the holes on the top and bottom.
The E5CN-@-500 is provided with a terminal cover.
E5CN
+
1
Control output 1
2
A
3
B
4
Analog input
B
5
+
+
Pt
TC
Two input power supplies are available: 100 to 240 VAC or 24 VDC.
Alarm output
11
6
ALM2/
12
7
Control output2
ALM1/heater
burnout
/Input error
13
8
14
9
Input power supply
15
10
Section 2-2
E53-CNHB
Event input/
Communications/
CT
CT
11
EV1
EV1
12
+
EV2
EV2
13
+
14
CT
15
E53-CNH03
RS-485
B(+)
11
A(−)
12
Do not
13
use
14
CT
15

Hide quick links: