Setting the SP Upper and Lower Limit Values
4-6-2

Setup

Setting the set point upper limit
Operation Procedure
1,2,3...
Initial setting level
Input type
Set point
upper limit
Setting the set point lower limit
Operation Procedure
1,2,3...
Set point lower
limit
54
To set the set point upper and lower limits, set in the "set point upper limit" and
"set point lower limit" parameters in the "initial setting level". This example
describes how to set the set point limitter "-200 to 1300 ° C" to input type K
thermocouple.
-200
-100
Set the "set point upper limit" parameter to "1000".
1. Press the
key for at least three seconds to move from the "operation
level" to the "initial setting level".
2. Select "set point upper limit".
3. Press the
or
Set the "set point lower limit" parameter to "-100".
1. Select "set point lower limit" in the "initial setting level".
2. Press the
or
Sensor range
Set point limitter
key to set the parameter to "1000".
key to set the parameter to "-100".
Section 4-6
1300
1000