8
Connecting the boiler on the flue gas side
This chapter explains how to connect the boiler on the flue
gas side.
8.1

Installing a vent pipe sealing collar

(accessory)

We recommend you use a vent pipe sealing
collar (
Fig. 45, [1]).
B Push the vent pipe as far as possible onto the draft
diverter outlet.
B Place the vent pipe sealing collar around the vent pipe
and draft diverter outlet so that it overlaps at the top.
B Place hose clamps (Fig. 45, [4]) over the vent pipe
sealing collar. One of the hose clamps must press onto
the draft diverter outlet and and one onto the vent pipe.
B Tighten hose clamps.
The vent pipe sealing collar must fit smoothly and firmly in
place after tightening the hose clamps.
Fig. 45 Installing the vent pipe
1
Vent pipe sealing collar
2
Flue gas temperature sensor
3
Sleeve
4
Vent pipe
5
hose clamps
6
Exhaust Manifold
A
2 × Vent pipe diameter, at least 28 22/64 inches
(720 mm)
Logano G315 - Subject to technical modifications
Connecting the boiler on the flue gas side
Retighten the hose clamps if required.
8.1.1
Installing a flue gas temperature sensor
(accessory)
B Weld a sleeve (Fig. 45, [3]) at a distance of two
(2) × vent pipe diameters (A) – min. 720 mm – from
the draft diverter in the vent pipe.
B Fit the flue gas temperature sensor (Fig. 45, [2]) as
described in the separate installation manual.
8
33