Mounting The Burner - Buderus Logano G315 Installation And Service Instructions Manual

Low-temperature oil/gas boiler
Table of Contents

Advertisement

10

Mounting the burner

10 Mounting the burner
This chapter explains the basic steps involved in fitting a
burner.
NOTICE: Risk of system damage from use of
incorrect burner.
B Only use burners that meet the technical
requirements of the oil/gas-fired boiler
Logano G315 (
B Close the burner door and seal with 4 machine screws
(M16 × 140) (
Chapter 7.8.4, page 28, Fig. 31, [5]).
Tighten the machine screws evenly crosswise.
You can obtain undrilled or predrilled burner
plates (hole pattern depends on burner) as
accessories from Buderus.
If you have ordered an undrilled burner plate, you will have
to machine this on site:
B Drill or cut the burner plate (
the required burner tube diameter Ø 10 5/8 inches
(270 mm).
B Drill holes for fastening the boiler using the burner
connecting flange as a template.
B Screw burner plate onto the burner door (seal with GP
sealant rope; diameter Ø 25/64 inches (10 mm)).
B Screw the burner to the burner plate.
B Cut out insulating rings to match the burner tube
diameter (
Fig. 52, [2]).
B Fill the remaining gap between the burner door thermal
insulation and the burner tube (
the appropriate insulating rings (
B Connect the vent connection to the burner to ensure
the inspection window remains free of deposits.
36
chapter 3, page 11).
Fig. 52, [1]) to match
Fig. 52, [4]) using
Fig. 52, [3]).
1
Fig. 52 Mounting the burner
Logano G315 - Subject to technical modifications
2
3
4
6 720 642 621-25.1o