Buderus Logano GC124 II/SP Installation And Service Instructions Manual page 52

Gas boiler
Table of Contents

Advertisement

16
Boiler inspection and maintenance
Performing final checks
14. Place boiler in operation as directed in
Chapter 11, page 26 to page 29.
15. For GC124 II: Follow instructions in
page 30 to page 34.
16. For GC124 SP: Follow instructions in
page 35 bis page 39.
17. Test low water alarm if installed.
18. Check area around boiler for hazards.
RISK OF FIRE
From flammable material or liquids.
The area around the boiler must be free
WARNING!
from flammable substances, gasoline
or any other flammable or corrosive va-
pors and liquids.
Maintain a minimum distance of
15 inches around the boiler.
RISK TO LIFE
from explosion of flammable gases.
After maintenance work leaks can oc-
WARNING!
cur in pipes and threaded fastenings.
Make a thorough check for leaks.
Use only approved leak testing agents
to search for leaks.
Complete the maintenance protocol to confirm that all
maintenace work has been conducted. Sign the mainte-
nance protocol and discuss it with the owner of the heat-
ing system.
52
Chapter 12,
Chapter 13,
Installation and maintenance instructions Gas Boiler Logano GC124 II/SP • Issue 07/2006
We reserve the right to make any changes due to technical modifications.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents