Figure 23 Example Of Lrv And Urv Interaction - Honeywell SMV 3000 User Manual

Smart multivariable transmitter
Hide thumbs Also See for SMV 3000:
Table of Contents

Advertisement

6.8
TempConf Configuration - PV3,
ATTENTION
Figure 23
66
For a reverse range, enter the upper range value as the LRV and the
lower range value as the URV. For example, to make a 0 to 500 °F
range a reverse range, enter 500 as the LRV and 0 as the URV.
The URV changes automatically to compensate for any changes in the
LRV and maintain the present span (URV – LRV). See Figure 23 for
an example.
If you must change both the LRV and URV, always change the LRV
first. However, if the change in the LRV would cause the URV to
exceed the URL, you would have to change the URV to narrow the
span before you could change the LRV
Example of LRV and URV Interaction
Current Range Settings
LRL
LRV
-328
-100
Range Settings After LRV is Changed to Zero (0)
LRL
LRV
-328
-100
0
SMV 3000 Transmitter User's Manual
Continued
SPAN
URV
257
600
SPAN
URV URL
600 700 842 o F
257
Continued on next page
URL
842 o F
1/99