6.8
TempConf Configuration - PV3,
Sensor Type
Table 15
d Factory setting.
ATTENTION
1/99
Identify and select the type of sensor that is connected to the transmitter as
its input for process temperature PV3. This will set the appropriate LRL
and URL data in the transmitter automatically.
Table 15 shows the pre-programmed temperature sensor types and the
rated measurement range limits for a given sensor selection.
Sensor Types for PV3 Process Temperature Input
Sensor Type
PT100 D d
Type E
Type J
Type K
Type T
Whenever you connect a different sensor as the transmitter's input, you
must also change the sensor type configuration to agree. Otherwise, range
setting errors may result.
SMV 3000 Transmitter User's Manual
Continued
Rated Temperature Range Limits
C
-200 to 450
0 to 1000
0 to 1200
-100 to 1250
-100 to 400
F
-328 to 842
32 to 1832
32 to 2192
-148 to 2282
-148 to 752