11.4
Diagnostic Messages,
Diagnostic Messages,
Table 31
continued
SMV Status
SCT Status Message SFC Display Message TDC Status Message
7-2
Input Suspect PV3
3-0
Invalid Database
7-4
NVM Fault PV3
8-4
Over Range PV3
9-0
PV4 (Flow) Algorithm
Parameters Invalid
3-3
PV4 in failsafe
1/99
Continued
Critical Status Diagnostic Message Table, Continued
OUTP 1
TAG ID.
SUSPCT INPUT PV3
TAG NO.
INVALID DATABASE
INVALID DATABASE
STATUS
TAG ID.
NVM FAULT PV3
NVM FAULT PV3
STATUS
TAG ID.
OVERRANGE PV3
OVERRANGE PV3
STATUS
TAG ID.#
STATUS 9-0
ALGPARM INVALID
-
STATUS 3-3
SMV 3000 Transmitter User's Manual
Possible Cause
-
PV3 Input data seems wrong.
Sensor reading is extremely
erratic.
Could be a process problem, but
it could also be a temperature
sensor or electronics module
problem.
Transmitter database was
incorrect at power-up.
PV3 nonvolatile memory fault.
Process temperature exceeds
PV3 range.
Configuration for selected
equation is not complete.
An algorithm diagnostic has
determined the flow to be invalid.
What to Do
• Cycle transmitter power OFF/ON.
• Check sensor leads for weak area
that may be ready to break or
loose connection.
•
Try communicating again.
•
Verify database configuration,
and then manually update non-
volatile memory.
Replace electronics module.
•
Check process temperature.
Reduce temperature, if required.
•
Replace temperature sensor, if
needed.
Check the flow configuration using
the SCT flow compensation wizard.
•
Resolve the conditions causing
the other diagnostic message.
•
Check all flow configuration
parameters.
Continued on next page
125