11.4
Diagnostic Messages,
Diagnostic Messages,
Table 31
continued
SMV Status
SCT Status Message SFC Display Message TDC Status Message
7-2
Input Suspect PV3
3-0
Invalid Database
7-4
NVM Fault PV3
8-4
Over Range PV3
9-0
PV4 (Flow) Algorithm
Parameters Invalid
3-3
PV4 in failsafe
1/99
Continued
Critical Status Diagnostic Message Table, Continued
OUTP 1
TAG ID.
SUSPCT INPUT PV3
TAG NO.
INVALID DATABASE
INVALID DATABASE
STATUS
TAG ID.
NVM FAULT PV3
NVM FAULT PV3
STATUS
TAG ID.
OVERRANGE PV3
OVERRANGE PV3
STATUS
TAG ID.#
STATUS 9-0
ALGPARM INVALID
-
STATUS 3-3
SMV 3000 Transmitter User's Manual
Possible Cause
-
PV3 Input data seems wrong.
Sensor reading is extremely
erratic.
Could be a process problem, but
it could also be a temperature
sensor or electronics module
problem.
Transmitter database was
incorrect at power-up.
PV3 nonvolatile memory fault.
Process temperature exceeds
PV3 range.
Configuration for selected
equation is not complete.
An algorithm diagnostic has
determined the flow to be invalid.
What to Do
• Cycle transmitter power OFF/ON.
• Check sensor leads for weak area
that may be ready to break or
loose connection.
Try communicating again.
Verify database configuration,
and then manually update non-
volatile memory.
Replace electronics module.
Check process temperature.
Reduce temperature, if required.
Replace temperature sensor, if
needed.
Check the flow configuration using
the SCT flow compensation wizard.
Resolve the conditions causing
the other diagnostic message.
Check all flow configuration
parameters.
Continued on next page
125