11.3

Troubleshooting Using the SCT

Summary
Table 30 Accessing SMV 3000 Diagnostic Information using the SCT
ATTENTION
1/99
Using the SCT in the on-line mode you can check the transmitter status,
identify diagnostic messages and access troubleshooting information so
you can clear fault conditions.
The SMV diagnostic messages fall into any one of the following general
categories:
Status (Informational)
Noncritical Status
Critical Status
Communications
Follow the steps in Table 30 to access diagnostic messages generated by
the SMV 3000 and procedures for clearing transmitter fault conditions.
Step
Connect the SCT to the SMV and establish communications. (See
1
Subsection 5.2 Establishing Communications for the procedure, if
necessary.)
Select the Status Tab Card (if not selected already) to display a
2
listing of the Gross Status and Detailed Status messages.
Refer to the SCT on-line user manual for descriptions of the status
3
messages and corrective actions to clear faults.
When critical status forces PV output into failsafe condition, record the
messages before you cycle transmitter power OFF/ON to clear failsafe
condition.
SMV 3000 Transmitter User's Manual