Honeywell SMV 3000 User Manual page 174

Smart multivariable transmitter
Hide thumbs Also See for SMV 3000:
Table of Contents

Advertisement

A.5
Configuration,
ATTENTION
DE_CONF Parameter
Table A-6
URL Parameter
Table A-7
ATTENTION
162
Continued
The actual engineering unit values available in a system will depend upon
the LCN software release. See Section 10 in the PM/APM Smartline
Transmitter Integration Manual for release dependent EU details.
While the DECONF selections are the same for all transmitters, the
corresponding SCT 3000 selections for PV Type may differ. Table A-6
compares the PV Type selections for SMV 3000 with PED DECONF
parameter selections for reference.
DECONF and PV Type Parameter Entry Comparison
IF PED DECONF entry is ...
PV
PV_SV
PV_DB
PV_SV_DB
Table A-7 lists example Upper Range Limits for a given SMV 3000
transmitter PV. Remember that you can enter the desired URL for the PV4
range through the SCT 3000, but URL for PV1, PV2, and PV3 is a read
only fixed value (determined by SMV model and process temperature
sensor type).
Example URLs for a SMV Transmitter Model SMA125.
IF Process Variable Number is...
PV1
PV2
PV3
PV4
If you leave the URL parameter blank, you can upload the transmitter
database through the detail display commands to resolve the resulting
database mismatch error. The URL is always part of the transmitter's
database.
SMV 3000 Transmitter User's Manual
THEN comparable SCT 3000 PV Type
entry can be any one of the following ...
Not Applicable for SMV 3000.
Not Applicable for SMV 3000.
PV1,
PV1 and PV2,
PV1 - PV3, or
PV1 - PV4
PV1 w/SV1,
PV1 and PV2 w/SV1
PV1 - PV3 w/SV1, or
PV1 - PV4 w/SV1
THEN URL is ...
400 inH2O
750 psia
850 C (varies per sensor type)
configurable
Continued on next page
1/99

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents