11.4
Diagnostic Messages,
Diagnostic Messages,
Table 32
continued
SMV Status
SCT Status Message SFC Display Message TDC Status Message
6-4
Output Mode PV1 (DP)
6-5
Output Mode PV2 (SP)
6-6
Output Mode PV3
(Temp)
6-7
Output Mode PV4 (Flow)
3-7
PV4 Independent
variable out of range
130
Continued
Non-Critical Status Diagnostic Message Table, Continued
STATUS
TAG ID.#
OUTPUT MODE PV1
OUTPUT MODE PV1
STATUS
TAG ID.#
OUTPUT MODE PV2
OUTPUT MODE PV2
STATUS
TAG ID.#
OUTPUT MODE PV3
OUTPUT MODE PV3
STATUS
TAG ID.#
OUTPUT MODE PV4
OUTPUT MODE PV4
-
STATUS 3-7
SMV 3000 Transmitter User's Manual
Possible Cause
Analog transmitter is operating as a
current source for PV1 output.
Analog transmitter is operating as a
current source for PV2 output.
Analog transmitter is operating as a
current source for PV3 output.
Analog transmitter is operating as a
current source for PV4 output.
For R250 Laminar Flow transmitters
only. Asserted when a PV is not
within the range of a term in the
laminar Flow equation.
What to Do
Exit Output Mode:
SCT – Press "Clear Output Mode"
button on the DP OutCal tab.
SFC – Press [
] and [
]
OUTPUT
CLR
keys.
Exit Output Mode:
SCT – Press "Clear Output Mode"
button on the AP OutCal tab.
SFC – Press [
] and [
]
OUTPUT
CLR
keys.
Exit Output Mode:
SCT – Press "Clear Output Mode"
button on the TEMP OutCal
tab.
SFC – Press [
] and [
]
OUTPUT
CLR
keys.
Exit Output Mode:
SCT – Press "Clear Output Mode"
button on the FLOW OutCal
tab.
SFC – Press [
] and [
]
OUTPUT
CLR
keys.
Check the value of every PV
against the ranges in the
Laminar Flow equation.
Redefine the equation, if
necessary.
1/99