Fireplace Placement Requirements
Minimum Framing Dimensions
A 1" clearance is required along the sides and back of the fireplace. The 1" stand-offs on the sides and 10-
1/2" stand-offs on the top of the fireplace are designed to separate the fireplace from the framing members.
These stand-offs may contact the framing members but no material may be placed between the stand-offs
5-1/2" Clearance Min.
(before firestop)
The fireplace enclosure
must not be less than
75" above the base of
the fireplace.
If using a remote
control or thermostat,
route the wire to a
location near the gas
line (include an extra 3'
length for hookup).
Gas line (3/8" M.P.T. or 1/2"
F.P.T.) should be routed 6-1/2"
behind the framing opening
and 2-3/8" above the base of
the fireplace (see "Gas Line
Connection" for details).
•
Fireplace must be installed on a level surface capable of supporting the fireplace and vent
•
Fireplace must be placed directly on wood or non-combustible surface (not on linoleum or carpet)
•
Due to the high temperature of the fireplace, it should be located out of traffic and away from furniture and
draperies.
This heater may be placed in a bedroom. Please be aware of the large amount of heat this appliance produces
when determining a location.
Travis Industries
Installation
Required Firestop (included with
the fireplace)
75" Min.
50-3/4"
24-3/8"
52"
(for qualified installers only)
4050114
NOTE: if venting directly to the rear,
make sure there is a min. 12" space
centered behind the fireplace.
3" Clearance Min. (after firestop)
1" Clearance min. to the sides
and below the vent (before or
after firestop).
Minimum 65-1/2" above the
base of the fireplace (includes
18" min. rise before elbow -
see the section "Horizontal
Termination Requirements")
Route the electrical line to a position
at the right rear of the fireplace.
NOTE: If using the power heat vent,
allow for the duct passage when
framing the enclosure.
1 0 0 - 0 1 1 4 9
9