Gas Line Requirements; Fuel; Gas Line Connection; Gas Inlet Pressure - FireplaceXtrordinair 44 DV XXL EF Manual

Built-in direct vent fireplace
Hide thumbs Also See for 44 DV XXL EF:
Table of Contents

Advertisement

1 2

Gas Line Requirements

!
The gas line must be installed in accordance with all local codes, if any; if not, follow ANSI 223.1 and the
requirements listed below.
!
The fireplace and gas control valve must be disconnected from the gas supply piping during any pressure
testing of that system at test pressures in excess of 1/2 psig. For pressures under 1/2 psig, isolate the gas
supply piping by closing the manual shutoff valve.
!
Leak test all gas line joints and the gas control valve prior to and after starting the fireplace.

Fuel

This fireplace is designed either for natural gas or for propane (but not for both). Check the sticker on the top
of the gas control valve to make sure the correct fuel is used.

Gas Line Connection

A manual shutoff valve is required for installation (within 3' of the heater or inside the fireplace).
T-Handle gas cocks are required in Massachusetts in compliance with code 248CMR.
Travis Industries
Installation
(for qualified installers only)
4050114
1 0 0 - 0 1 1 4 9