Fireplace Placement Requirements

Fireplace must be installed on a level surface capable of supporting the fireplace and vent
Fireplace must be placed directly on wood or non-combustible surface (not on linoleum or carpet)
Fireplace should be located out of traffic and away from furniture and avoid burns.
Fireplace must be placed so the gaps below and above the glass frame do not become blocked.
Fireplace may be placed in a bedroom. Please be aware of the large amount of heat this appliance produces
when determining a location.

Clearances

(a) Clearance to Side of Fireplace 1/2" (13mm). Do not place insulation in this space.
NOTE: Drywall (or other combustible) may contact the first ½" of the sides of the fireplace.
(b) Clearance to Back of Fireplace 1/2" (13mm). Do not place insulation in this space.
(c) When installed, walls in front of the fireplace must be a minimum 0" (0mm) to the side of the fireplace
standoffs.

Raised Fireplaces

The fireplace (and hearth, if desired) may be placed on a platform designed to support the fireplace and vent.
The base of the fireplace must be a minimum 60" (1524mm) below the room ceiling.
The top of the control door (firebox opening) is approximately 8-3/4" (223mm) above the base of
the fireplace. For a typical raised fireplace of 36" (915mm), place the fireplace on a platform 27-
1/4" (693mm) tall.