Function Mode; Output Frequency Setting/Monitor; Acceleration/Deceleration Time - Omron JX User Manual

200 v class three-phase input 0.2 to 7.5 kw; 200 v class single-phase input 0.2 to 2.2 kw; 400 v class three-phase input 0.4 to 7.5 kw
Table of Contents

Advertisement

4-2 Function Mode

4-2 Function Mode
<Group F: Basic Function Parameter>

Output Frequency Setting/Monitor

•Set the Inverter output frequency.
•With the frequency reference set to the Digital Operator ([A001] = 02), you can set the output
4
frequency in F001. For other methods, refer to the [A001] section in "Frequency Reference
Selection" (page 4-8).
•If a frequency is set in [F001], the same value is automatically set in multi-step speed reference 0
[A020]. To set the 2nd speed reference, use [A220], or use [F001] with the SET terminal turned on.
To set by using the SET terminal, allocate 08 (SET) to the desired multi-function input.
Parameter No.
F001
A020
*
A220
Related parameters
* To switch to the 2nd multi-step speed, allocate 08 (SET) to the multi-function input terminal and then turn it on.

Acceleration/Deceleration Time

Set an acceleration/deceleration time for the motor. For a slow transition, set a large value, and for
a fast transition, set a small one.
Parameter No.
F002
*
F202
F003
*
F203
Related parameters
* To switch to 2nd acceleration/deceleration time 1, allocate 08 (SET) to the multi-function input terminal and then
turn it on.
4-6
Function name
Output frequency
setting/monitor
Multi-step speed
0.0/Starting frequency to Max.
reference 0
frequency
2nd multi-step
speed reference 0
Function name
Acceleration time 1
2nd acceleration time 1
0.01 to 3000
Deceleration time 1
2nd deceleration time 1
Data
Default setting
A001, A201, C001 to C005
Data
Default setting
A004, A204, C001 to C005
Unit
6.0
Hz
Unit
10.0
s

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents