Frequency Jump Function - Omron JX User Manual

200 v class three-phase input 0.2 to 7.5 kw; 200 v class single-phase input 0.2 to 2.2 kw; 400 v class three-phase input 0.4 to 7.5 kw
Table of Contents

Advertisement

•You can set both upper/lower limits to the set frequency. This function does not accept any
frequency reference beyond the set limits.
•Set the upper limit first.
Make sure the upper limit (A061/A261) is higher than the lower limit (A062/A262).
•Neither limit would work if set to 0 Hz.
If the lower limit is set, the set value is prioritized even if 0 V (4 mA) is input for frequency reference.

Frequency Jump Function

This function helps avoid resonant points of loaded machines.
Parameter No.
Function name
A063
Jump frequency 1
A065
Jump frequency 2
A067
Jump frequency 3
A064
Jump frequency width 1
A066
Jump frequency width 2
A068
Jump frequency width 3
Related parameters
•The output frequency cannot be set within the frequency range set in the frequency jump function.
•The output frequency only pass through the jump frequency during acceleration and deceleration
process, but if the frequency reference is set inside this area the output will move automatically out
of this jump area setting a higher or lower frequency depending if inverter is accelerating or
decelerating.
f
Set frequency (Hz)
Max. frequency
A004/A204
A061
A062
0V
4mA
0.0 to 400.0
0.0 to 10.0
Output
frequency
A067
A065
A064
A063
A064
Frequency
reference
10V
20mA
Data
Default setting
C001 to C005
A068
A068
A066
A066
Frequency
reference
4-2 Function Mode
Unit
0.0
Hz
0.5
4-21
4