Holding Register Number List - Omron JX User Manual

200 v class three-phase input 0.2 to 7.5 kw; 200 v class single-phase input 0.2 to 2.2 kw; 400 v class three-phase input 0.4 to 7.5 kw
Table of Contents

Advertisement

4-2 Function Mode
Coil No.
0017h
0018h
0019h
001Ah
001Bh
001Ch
001Dh
4
001Eh
001Fh
*1. When either the control circuit terminal block or the coil is turned ON, these settings are ON.
The control circuit terminal block has the priority for the multi-function input.
If the master cannot reset the coil ON status due to communication disconnection, turn the control circuit
terminal block from ON to OFF in order to turn OFF the coil
*2. The content of a communications error is retained until a fault reset is input. (Available to reset during
operation)

Holding Register Number List

Register
Function name
No.
Frequency reference
0002h
(Enable when A001 = 03)
0003h
Inverter status
PID feedback
0005h
(Enable when A076 = 02)
1002h
Output frequency monitor
1003h
Output current monitor
1004h
Rotation direction monitor
1005h
PID feedback value monitor
(A075 PID scale)
1006h
1007h
Multi-function input monitor
4-78
Item
Frequency arrival signal
(Over set frequency)
Frequency arrival signal
(At a constant speed)
Signal during RUN
Data writing
CRC error
Overrun error
Framing error
Parity error
Check sum error
Parameter
No.
d001
d002
d003
d004
(MSB)
d004
(LSB)
d005
R/W
R
1: ON
R
0: OFF
R
1: Writing
R
0: Normal
R
R
1: Error
R
*2
0: No error
R
R
R/W
Monitor or data range
Function
R/W
0 to 4000
00: Default
01: (Reserved)
02: Stop
03: Run
04: Free-run stop (FRS)
R
05: Jogging
06: DC injection braking
07: Retry
08: Trip
09: Undervoltage
R/W
0 to 1000
R
0 to 4000
R
0 to 2000
00: Stop
R
01: Forward
02: Reverse
R
0 to 999900
0 to 63
R
Multi-function input status, Bit 0 = [1] to
Bit 4 = [5]
Description
Resolution
0.1 [Hz]
0.1 [%]
0.1 [Hz]
0.1 [%]
0.01 [%]