Wiring To The Power Supply And Motor - Omron JX User Manual

200 v class three-phase input 0.2 to 7.5 kw; 200 v class single-phase input 0.2 to 2.2 kw; 400 v class three-phase input 0.4 to 7.5 kw
Table of Contents

Advertisement

2-2 Wiring

Wiring to the Power Supply and Motor

(Example) JX-A2004
2
Power supply Ground
Motor
earth
•Do not connect the power supply other than to R/L1, S/L2, or T/L3.
•Do not remove the short-circuit bar between P/+2 and +1, except when a DC reactor is connected.
Note 1: Install an earth leakage breaker on the power supply input side.
2-10
Main circuit terminal block (input side)
Main circuit terminal block (output side)
R/L1 S/L2 T/L3
N/- P/+
+1
U/T1 V/T2 W/T3
Motor
(Select an earth leakage breaker having a higher sensed leakage current and avoid
unnecessary operation.)
If the wiring between the Inverter and the motor is too long (longer than 10 m), the motors
thermal relay may malfunction due to harmonics. Install an AC reactor on the Inverter output
side, or use a current sensor instead of the motors thermal relay.
(Example) JX-A2037
Main circuit terminal block (input side)
Main circuit terminal block (output side)
Power supply Ground
R/L1 S/L2 T/L3
U/T1 V/T2 W/T3 N/- P/+
Motor
earth
Motor
+1