Standard Specification List; 3-Phase 200-V Class; 3-Phase 400-V Class - Omron JX User Manual

200 v class three-phase input 0.2 to 7.5 kw; 200 v class single-phase input 0.2 to 2.2 kw; 400 v class three-phase input 0.4 to 7.5 kw
Table of Contents

Advertisement

7-1 Standard Specification List

7Specifications
7-1 Standard Specification List

3-phase 200-V Class

Item
Model name (JX-)
Applicable motor
*1
capacity
Rated output
capacity (kVA)
Rated input voltage
Built-in filter
Rated input current (A)
Rated output voltage
Rated output current (A)
Weight [kg]
Cooling method
7
deceleration
Braking
At capacitor feedback
torque
DC injection braking

3-phase 400-V Class

Item
Model name (JX-)
Applicable motor
*1
capacity
Rated output capacity
(kVA)
Rated input voltage
Built-in filter
Rated input current (A)
Rated output voltage
Rated output current (A)
Weight [kg]
Cooling method
At short-time
deceleration
Braking
At capacitor feedback
torque
DC injection braking
7-2
A2002
kW
0.2
HP
1/4
200V
0.4
240 V
0.5
1.8
*2
1.4
0.8
Self-cooling
At short-time
*3
A4004
kW
0.4
HP
1/2
380 V
0.9
480 V
1.2
2.0
*2
1.5
1.5
Self-cooling
*3
3-phase 200-V class
A2004
A2007
A2015
0.4
0.75
1.5
1/2
1
2
0.9
1.3
2.4
1.0
1.6
2.9
3-phase (3-wire) 200 V -15% to 240 V +10%, 50/60 Hz ±5%
3.4
5.2
9.3
3-phase: 200 to 240 V (Proportional to input voltage)
2.6
4.0
7.1
0.9
1.1
2.2
Approx. 50%
Injection braking frequency/time, braking force variable,
frequency control available
3-phase 400-V class
A4007
A4015
A4022
0.75
1.5
1
2
1.6
2.5
2.0
3.1
3-phase (3-wire) 380 V -15% to 480 V +10%, 50/60 Hz ±5%
EMC filter (EN61800-3 category C3)
3.3
5.0
3-phase: 380 to 480 V (Proportional to input voltage)
2.5
3.8
2.3
2.4
Approx. 50%
Approx. 20% to 40%
Injection braking frequency/time, braking force variable,
frequency control available
A2022
A2037
A2055
2.2
3.7
5.5
3
5
7.5
3.4
5.5
8.3
4.1
6.6
9.9
-
13.0
20.0
30.0
10.0
15.9
24.0
2.4
2.4
4.2
Forced-air-cooling
Approx. 20%
Approx. 20% to
40%
A4040
A4055
2.2
4.0
5.5
3
5
7.5
3.6
5.6
8.5
4.5
7.1
10.8
7.0
11.0
16.5
5.5
8.6
13.0
2.4
2.4
4.2
Forced-air-cooling
Approx. 20%
A2075
7.5
10
11.0
13.3
40.0
32.0
4.2
A4075
7.5
10
10.5
13.3
20.0
16.0
4.2

Hide quick links:

Advertisement

Table of Contents
loading