Register Number List; Coil Number List - Omron JX User Manual

200 v class three-phase input 0.2 to 7.5 kw; 200 v class single-phase input 0.2 to 2.2 kw; 400 v class three-phase input 0.4 to 7.5 kw
Table of Contents

Advertisement

Register Number List

R/W in the list shows whether the coil or holding register accepts reading and/or writing.
R: Read only

Coil Number List

Coil No.
0000h
Not used
0001h
RUN commands
0002h
Rotation direction command
0003h
External Trip (EXT)
0004h
Trip reset (RS)
0005h
Not used
0006h
Not used
0007h
Multi-function input 1
0008h
Multi-function input 2
0009h
Multi-function input 3
000Ah
Multi-function input 4
000Bh
Multi-function input 5
000Dh
Not used
000Eh
Operation status
000Fh
Rotation direction
0010h
Inverter ready
0011h
Not used
0012h
Not used
0013h
Not used
0014h
Alarm signal
0015h
Excessive PID deviation signal
0016h
Overload warning signal
*1. When either the control circuit terminal block or the coil is turned ON, these settings are ON.
The control circuit terminal block has the priority for the multi-function input.
If the master cannot reset the coil ON status due to communication disconnection, turn the control circuit
terminal block from ON to OFF in order to turn OFF the coil
*2. The content of a communications error is retained until a fault reset is input. (Available to reset during
operation)
R/W: Read and write enabled
Item
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R
R
R
R
R
R
4-2 Function Mode
Description
1: RUN
0: Stop (Enabled when A002 = 03)
1: Reverse
0: Forward (Enabled when A002 = 03)
1: Trip
1: Reset
1: ON
*1
0: OFF
1: ON
*1
0: OFF
1: ON
*1
0: OFF
1: ON
*1
0: OFF
1: ON
*1
0: OFF
1: RUN
0: Stop (Interlocked with d003)
1: Reverse
0: Forward (Interlocked with d003)
1: Ready
0: Not ready
1: During trip
0: Normal
1: ON
0: OFF
4
4-77