Selecting The Sequence Input Method (Sink/Source Logic) - Omron JX User Manual

200 v class three-phase input 0.2 to 7.5 kw; 200 v class single-phase input 0.2 to 2.2 kw; 400 v class three-phase input 0.4 to 7.5 kw
Table of Contents

Advertisement

Selecting the Sequence Input Method (Sink/Source Logic)

Logic Selection Method for the Multi-function Input Terminals
When the internal power supply is used, you can switch the logic by rearranging the short-circuit bar
on the control circuit terminal block. The default setting is sink logic.
<Sink Logic>
1
Note 1: Remove the short-circuit bar when the external power supply is used.
Inside the Inverter
When Internal interface power supply is used
+V
COM
Output unit etc.
COM
0V
Output unit etc.
L
PCS P24 CM2
Short-circuit bar
P24
Short-circuit
PCS
24 V DC
bar
L
1
5
Inverter
P24
PCS
Short-circuit
24 V DC
bar
L
1
5
Inverter
<Source Logic>
1
L
PCS P24 CM2
Short-circuit bar
When external power supply is used
+V
DC24V
COM
Output unit etc.
\
COM
0V
Output unit etc.
2-2 Wiring
P24
PCS
24 V DC
L
1
5
Inverter
P24
24 V DC
PCS
24 V DC
L
1
5
Inverter
2-13
2

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents