Motor Capacity And Pole Number; Stabilization Parameter - Omron JX User Manual

200 v class three-phase input 0.2 to 7.5 kw; 200 v class single-phase input 0.2 to 2.2 kw; 400 v class three-phase input 0.4 to 7.5 kw
Table of Contents

Advertisement

<Group H: Motor Control Parameters>

Motor Capacity and Pole Number

Set the capacity and number of poles of the motor connected to the Inverter.
•With incorrect parameters set, appropriate operation cannot be ensured.
Parameter No.
Function name
H003
Motor capacity selection
*
H203
2nd motor capacity selection
H004
Motor pole number selection
*
H204
2nd motor pole number selection
Related parameters
* To switch to the 2nd control, allocate 08 (SET) to the multi-function input terminal and then turn it on.

Stabilization Parameter

This function helps to reduce motor hunting.
Parameter No.
Function name
H006
Stabilization parameter
*
H206
2nd stabilization parameter
Related parameters
* To switch to the 2nd control, allocate 08 (SET) to the multi-function input terminal and then turn it on.
•In case of motor hunting, check whether the motor capacity selection (H003/H203) and motor pole
number selection (H004/H204) match your motor. If they do not, match them.
•For adjustment, raise the stabilization parameter (H006) by degrees. If this increases motor
hunting, lower it by degrees.
•When using the automatic torque boost (A041/A241 = 01), if motor hunting occurs in a low speed
range, lower the manual torque boost voltage (A042/A242) and manual torque boost frequency
(A043/A243).
•Other than this function, the following methods are suggested to reduce hunting:
Lower the carrier frequency (b083)
Lower the output voltage gain (A045)
Parameter No.
Function name
A045
Output voltage gain
b083
Carrier frequency
H006/H206
Stabilization parameter
Data
200-V class
0.2/0.4/0.75/1.5/2.2/3.7/
5.5/7.5
400-V class
0.4/0.75/1.5/2.2/3.7/5.5/7.5
2/4/6/8
A041 to A045, A241 to A244
Data
0. to 255.
Data
20. to 100.
2.0 to 12.0
0. to 255.
4-2 Function Mode
Default setting
Inverter capacity
4
Default setting
100
100
A045, b083
Description
Unit: %
(Lower this in motor hunting.)
Unit: kHz
(Lower this in motor hunting.)
Adjust this in motor hunting.
Unit
kW
4
Pole
Unit
4-63

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents