4-2 Function Mode

Starting Frequency

Set the frequency to start Inverter output with the RUN signal turned on.
Parameter No.
Function name
Data
Default setting
Unit
b082
Starting frequency
0.5 to 9.9
1.5
Hz
•Use mainly to adjust the starting torque.
•With the starting frequency set high, the starting current increases. Therefore, the current may
exceed the overload limit and cause an overcurrent trip
.
FW
4
Output frequency
b082
Output voltage
4-39