Heater Burnout And Ssr Failure Detection Current Value Read: Rw - Omron E5ZE-8 Communications Manual

Multipoint temperature controller
Table of Contents

Advertisement

Heater Burnout and SSR Failure Detection Current Value
Response
Communications Example
Command
@
0
Response
5-4
Heater Burnout and SSR Failure Detection Current Value
Read: RW
Function
Command
Unit
@
1
x16
Response
Unit
@
1
x16
@
x16
In this example, the E5ZE is operated with Heater Burnout and SSR Failure
Detection Current Value Write (WW) under the following conditions.
Unit no.: 1
Control Point: 3
Heater Burnout Detection Current Value: 25.0 A
1
W
W
0
@
0
This command is used to read the current value set at a control point to be
used by the E5ZE to detect heater burnout or SSR failures.
Always 0
R
W
x16
0
Header code
R
W
End code
0
x16
x16
Header code
1. The response block for Heater Burnout and SSR Failure Detection Current
Value Read (RW) does not include read data if the end code of the re-
sponse block is other than 00.
W
W
Unit
1
x16
0
Header code
3
0
0
0
2
Heater
25.0 A
burnout
1
W
W
0
0
Normal end
Control
0
Data code
point
Read data
Detection current value
2
1
1
x16
0
x10
x10
End code
FCS
x16
1
x16
0
5
0
4
5
*
s
4
1
*
FCS
Terminator
00: Heater burnout detection (HB alarm)
01: SSR failure detection (HS alarm)
FCS
-1
x10
0
x10
Decimal point
Section 5-4
*
s
Terminator
*
s
s
*
s
Terminator
145