Output Operation (Normal/Reverse) Write: Wu - Omron E5ZE-8 Communications Manual

Multipoint temperature controller
Table of Contents

Advertisement

Output Operation (Normal/Reverse) Write: WU

3-13 Output Operation (Normal/Reverse) Write: WU

Function
Setting Data Range
Command
Unit
@
1
x16
x16
0
Header code
Response
Communications Example
This command is used to designate the normal or reverse operation of a con-
trol point.
1. Output Operation Write (WU) enables the E5ZE in heating and cooling
control operation to change its heating - side control to cooling - side control
and vice versa at a control point simultaneously.
2. Output Operation Write (WU) cannot be used at a control point in manual
operation, control operation or auto - tuning operation.
Default
Setting code
Always 00
W
U
0
0
Bit number
@
x16
In this example, the E5ZE is operated with Output Operation Write (WU)
under the following conditions.
Unit no.: 1
Control Points 0, 2, 4, and 6: Direct operation
Control Points 1, 3, 5, and 7: Reverse operation
0000 (All control points in reverse operation)
00 to FF
0
0
0
x16
3
Data code
7
6
5
4
3
W
U
Unit
1
0
x16
Header code
Setting data
Setting
0
code
2
1
0
x16
x16
x16
Control point
2
1
0
Point 0
Point 1
Point 2
Point 3
Point 4
Point 5
Point 6
Point 7
End code
FCS
1
0
x16
x16
Section 3-13
*
s
FCS
Terminator
Bit
Normal Reverse
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
*
s
Terminator
101

Advertisement

Table of Contents
loading