Omron E5ZE-8 Communications Manual page 33

Multipoint temperature controller
Table of Contents

Advertisement

DeviceNet Explicit Messages Set Values and Measurement
Variable Type: 88
No.
Address Set value or measurement value
1
XY00
Set point (read only)
2
XY01
Alarm 1 temperature (See note 1.) 0000
3
XY02
Alarm 2 temperature (See note 1.) 0000
4
XY03
Proportional band
5
XY04
Integral time
6
XY05
Derivative time
7
XY06
Heating hysteresis
8
XY07
Input shift value
9
XY08
Heater burnout detection current
10
XY09
Control period (heating)
11
XY0A
Manual reset value
12
XY0B
Heating output variable lower limit
13
XY0C
Heating output variable upper limit 03E8
14
XY0D
Ramp value (See note 1.)
15
XY0E
Ramp time unit (See note 1.)
16
XY0F
Output variable change rate limit
17
XY10
Dead band
18
XY11
Cooling coefficient
19
XY12
Cooling hysteresis
20
XY13
Cooling control period
21
XY14
Cooling output variable lower limit
22
XY15
Cooling output variable upper limit 03E8
23
XY16
Fuzzy strength
24
XY17
Fuzzy scale 1
25
XY18
Fuzzy scale 2
Default
0000
0000
0000
0000
See note
3
0000
0000
0002
01F4
0000
0000
0000
0000
0000
000A
See note
3
0002
0000
0032
270F
270F
• Set the values of X and Y in the addresses as follows:
X: Control point number (0 to 7). Set " A " for all control points.
Y: Memory bank number (0 to 7). Set " 8 " for the current memory bank or
" A " for all memory banks. The setting A is valid for writing only.
X and Y cannot both be set to A at the same time.
Example: To set the alarm 1 temperature in memory bank 3 for control
point 5, the address would be 5301 (hex).
• Set values cannot be written while auto - tuning is being executed.
Data setting or monitoring range
Depends on the input type and setting
unit. (Refer to page 25.)
Depends on setting unit. (Refer to
page 25.)
Range: 0000 to 270F (0.0 to 999.9)
Unit:
0.1 C/ F
Range: 0000 to 0F9F (0 to 3999)
Unit:
1 s
Range: 0000 to 03E7 (0.0 to 99.9)
Unit:
0.1 C/ F
Range: FC19 to 03E7 (-99.9 to 99.9)
Unit:
0.1 C/ F
Range: 0000 to 01F4 (0.0 to 50.0)
Unit:
0.1 A
Range: 0001 to 0063 (0 to 99)
Unit:
1 s
Range: 0000 to 03E8 (0.0 to 100.0)
Unit:
0.1%
Range: 0000 to 03E7 (0.0 to 99.9)
Unit:
0.1
0000: s, 0001: min, or 0002: hr
Range: 000 to 03E8 (0.0 to 100.0)
Unit:
0.1% per sampling period
Range: FC19 to 03E7 (-999 to 999)
Unit:
1 C/ F
Range: 0000 to 0064 (0.0 to 10.0)
Unit:
0.1
Range: 0000 to 03E7 (0.0 to 99.9)
Unit:
0.1 C/ F
Range: 0001 to 0063 (0 to 99)
Unit:
1 s
Range: 0000 to 03E8 (0.0 to 100.0)
Unit:
0.1%
Range: 0000 to 0063 (0 to 99)
Unit:
1%
Range: 0002 to 270F (0.2 to 999.9)
Unit:
0.1 C/ F
Range: 0014 to 270F (0.20 to 99.99)
Unit:
0.01
Section 4-4
Data type
Numeric
Read/write
29