Operating Status - Omron E5ZE-8 Communications Manual

Multipoint temperature controller
Table of Contents

Advertisement

Reading Status
Example
3-3-3

Operating Status

Temperature Controller Ready Flag
12
If no control points are being auto - tuned, and then auto - tuning begins for con-
trol point 3, the contents of the corresponding word in the PC will change as
follows:
0000000000000000
When auto - tuning for control point 3 has been completed, the contents of the
corresponding word will return to 0000000000000000.
The status data showing whether an error has occurred in the E5ZE is
expressed in the contents of the corresponding word in the PC to which the
Master Unit is mounted.
Operating status
Leftmost bit
Outside Temperature
Display Range Flag
This bit changes from 0 to 1
if any of bits 0 to 8 changes
from 0 to 1.
The following table provides the meaning and operation of the operating sta-
tus flags.
Flag name
Temperature Controller
Ready Flag
Outside Temperature Dis-
play Range Flag
Output Area Error Flag (See
note 1.)
Temperature Control Internal
Transmission Error Flag (See
note 1.)
Temperature Controller Error
Flag
Input Error Flag
Process Value Overflow Flag This flag changes from 0 to 1 if the process value is
®
1000000000001000
Control point 3 is
being auto-tuned.
Rightmost bit
Heater Current Overflow Flag
Process Value Underflow Flag
Process Value Overflow Flag
Input Error Flag
Temperature Controller Error Flag
Temperature Control Internal Transmission Error Flag
Output Area Error Flag
This flag changes from 0 to 1 when the E5ZE power is
turned ON and DeviceNet communications are
enabled.
After checking that this flag is ON, execute the pro-
gram to start using I/O data.
This flag changes from 0 to 1 if the process value
exceeds 3200.0 F when a W/Re5-26 thermocouple
sensor is being used and the setting unit is 0.1 C/ F.
This flag changes from 0 to 1 if the output data from
the Master is not reflected in the E5ZE due to the
operating mode.
This flag changes from 0 to 1 if the remote I/O func-
tion has not been processed properly in the E5ZE.
This flag changes from 0 to 1 if there is an error in the
Temperature Controller, such as an AD converter
error or memory error.
This flag changes from 0 to 1 if the temperature sen-
sor is disconnected or short-circuited.
more than the maximum value of the setting range.
(See note 2.)
Section 3-3
Meaning

Advertisement

Table of Contents
loading

Table of Contents