Omron E5ZE-8 Communications Manual page 29

Multipoint temperature controller
Table of Contents

Advertisement

DeviceNet Explicit Messages Set Values and Measurement
No.
Address
Set value or measurement value
113
00A4
Control point 0 dead band
114
00A5
Control point 1 dead band
115
00A6
Control point 2 dead band
116
00A7
Control point 3 dead band
117
00A8
Control point 4 dead band
118
00A9
Control point 5 dead band
119
00AA
Control point 6 dead band
120
00AB
Control point 7 dead band
121
00B0
Control point 0 fuzzy strength
122
00B1
Control point 1 fuzzy strength
123
00B2
Control point 2 fuzzy strength
124
00B3
Control point 3 fuzzy strength
125
00B4
Control point 4 fuzzy strength
126
00B5
Control point 5 fuzzy strength
127
00B6
Control point 6 fuzzy strength
128
00B7
Control point 7 fuzzy strength
Temperature
sensor
K
FF38 to 0514
(-200 to 1300)
J
FF9C to 0352
(-100 to 850)
R
0000 to 06A4
(0 to 1700)
S
0000 to 06A4
(0 to 1700)
T
FF38 to 0190
(-200 to 400)
E
0000 to 0258
(0 to 600)
B
0064 to 0708
(100 to 1800)
N
0000 to 0514
(0 to 1200)
L
FF9C to 0352
(-100 to 850)
U
FF38 to 0190
(-200 to 400)
W/Re5-26
0000 to 08FC
(0 to 2300)
Numeric data for the values in the above table is all expressed as 16 - bit
signed binary (two ' s complement for negative values)
Note
1. Numeric data cannot be modified during auto - tuning.
2. Auto - tuning cannot be executed when operation is stopped. The sequen-
tial auto - tuning function is not supported with DeviceNet communications.
3. If an instruction to stop operation is executed during auto - tuning, operation
will stop after auto - tuning is cancelled.
4. The setting ranges vary depending on the setting unit used, as shown in
the following table.
Setting unit (1)
C
FED4 to 08FC
(-300 to 2300)
FF9C to 05DC
(-100 to 1500)
0000 to 0BB8
(0 to 3000)
0000 to 0BB8
(0 to 3000)
FED4 to 02BC
(-200 to 700)
0000 to 044C
(0 to 1100)
012C to 0BB8
(300 to 3000)
0000 to 08FC
(0 to 2300)
FF9C to 05DC
(-100 to 1500)
FED4 to 02BC
(-300 to 700)
0020 to 1004
(0 to 4100)
Data setting or monitoring range
Range: FC19 to 03E7 (-999 to 999)
(See note 1.)
Unit:
1 C or F
Default: 0000 (0)
Range: 0000 to 0063 (0 to 99)
(See note 1.)
Unit:
1%
Default: 0032 (50)
Setting range
F
F830 to 32C8
(-200.0 to 1300.0)
FC18 to 2134
(-100.0 to 850.0)
0000 to 4268
(0.0 to 1700.0)
0000 to 4268
(0.0 to 1700.0)
F830 to 0FA0
(-200.0 to 400.0)
0000 to 1770
(0.0 to 600.0)
03E8 to 4650
(100.0 to 1800.0)
0000 to 32C8
(0.0 to 1300.0)
FC18 to 2134
(-100.0 to 850.0)
F830 to 0FA0
(-200.0 to 400.0)
0000 to 59D8
(0.0 to 2300.0)
Numeric
Read/write
Numeric
Read/write
Setting unit (0.1)
C
F448 to 59D8
(-300.0 to 2300.0)
FC18 to 3A98
(-100.0 to 1500.0)
0000 to 7530
(0.0 to 3000.0)
0000 to 7530
(0.0 to 3000.0)
F448 to 1B58
(-300.0 to 700.0)
0000 to 2AF8
(0.0 to 1100.0)
0BB8 to 7530
(300.0 to 3000.0)
0000 to 59D8
(0.0 to 2300.0)
FC18 to 3A98
(-100.0 to 1500.0)
F448 to 1B58
(-300.0 to 700.0)
0140 to 7D00
(32 to 3200.0)
Section 4-4
Data type
F
25